Compare two stated load scenarios
Build a current budget for devices on one common DC supply rail. Describe two operating scenarios and enter each device’s per-unit current in each scenario. The calculator totals current and input power separately for A and B.
Use device data at the voltage and state you are evaluating. Different supply voltages need separate budgets. These are sums of stated loads, not recommendations for a power supply or a rating for an access-control circuit.
Choose states that occur together
Scenario A might describe normal holding. Scenario B might describe a specific lock starting while the controller and other locks remain in their holding states. Define the actual combination instead of assuming that every device’s largest current occurs at the same time.
When two identical devices have different states in one scenario, put them on separate rows. A row’s quantity multiplies the same per-unit currents for both scenarios. Enter 0 explicitly for a device that is off; a missing current is an input error.
Startup and holding are not interchangeable. A static budget can compare a stated startup load with a stated holding load, but it does not determine startup duration, sequencing, output transient response, or whether a power supply can deliver that pulse.
Sum currents and calculate power
For n rows, common voltage V, quantity qᵢ, and per-unit current Iᵢ in a particular scenario:
Total current = Σ(qᵢ × Iᵢ)
Total input power = V × total current
The two scenarios are alternatives; their currents are not added together. The currents must describe loads on the same supply rail. Do not mix a device’s input current with its downstream output current in the same budget or count the same load twice.
Units and software limits
Voltage is in volts DC and must be positive. Currents are nonnegative decimal amperes, not milliamperes. For example, 150 mA is entered as 0.15 A. Quantities are whole numbers from 1 to 1,000; up to 20 rows are supported. Those are software limits, not circuit limits.
Names and scenario descriptions accept up to 64 characters. Numeric inputs accept up to 64 characters and 12 decimal places, without fractions, commas, or scientific notation. Results display three decimal places using half-up rounding. Exact totals are also shown; rounding does not add reserve capacity.
Worked example
This example uses hypothetical values, not product ratings:
- Common supply: 12 V DC.
- Two identical locks: 0.15 A each holding in A, 0.6 A each starting together in B.
- One controller: 0.1 A in both scenarios.
For A, 2 × 0.15 + 1 × 0.1 = 0.4 A, with 12 × 0.4 = 4.8 W.
For B, 2 × 0.6 + 1 × 0.1 = 1.3 A, with 12 × 1.3 = 15.6 W.
Displays are 0.400 A / 4.800 W for A and 1.300 A / 15.600 W for B. These totals do not establish the required supply rating. They assume both locks actually start together in B; a different sequence requires different row currents or scenarios.
Use the budget for the next check
Check the applicable equipment’s current data, rated outputs, per-output limits, temperature derating, reserve requirements, battery-charging load, and protection requirements. Add omitted loads deliberately. The tool does not assume a universal safety factor or allowable utilization percentage.
Wire loss and terminal voltage need a separate circuit model. Use the two-wire DC voltage drop calculator for one equal outgoing/return run carrying a stated current. A network with branches or loads distributed along a cable needs segment-by-segment analysis.
FAQs
Can I enter the same description and current twice?
You can compare identical scenarios, but doing so adds no new load case. Give each scenario enough detail to identify what the currents represent.
Does the result include power-supply inefficiency?
No. V × I describes the listed load input power at the common rail. AC input power, conversion losses, charging loads, and other supply requirements must be evaluated separately.
Sources
OpenStax, University Physics Volume 2, §10.2 explains how branch currents combine. §9.5, Electrical energy and power explains electrical power as voltage times current. These support the arithmetic and units, not a particular device current or supply selection.