DC branch network calculator

Calculate segment currents, node voltages, and conductor loss in a tree of stated constant-current DC loads.

Your inputs

Use decimal values in the labeled units. Fractions, scientific notation, and missing values are not treated as valid numbers.

One parent node, segment loop resistance (Ω), local current (A) per line. Nodes are numbered from 1 in row order. Parent 0 is the source; other parents must be earlier nodes. Up to 30 nodes.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

Your results will appear here after calculation.

A rooted tree of constant-current DC loads. Every segment resistance includes its complete outgoing and return path; no shared returns, loops, voltage-dependent loads, or source droop are solved. Nonpositive node voltage flags an unusable stated operating point.

Account for current shared by upstream segments

A cable segment feeding several downstream loads carries their combined current. Applying one end-load current to every segment can understate upstream voltage drop. This tool calculates a rooted tree: one source, separate parent-to-child segments, and a stated local constant-current load at each node.

Number nodes in row order, starting at 1. Parent 0 is the source; any other parent must be an earlier node. Enter the complete loop resistance for each segment, including its outgoing and return conductors. This differs from the single-conductor resistance input in the two-wire voltage drop calculator.

Work backward for current, forward for voltage

Segment current = local node current + all descendant load currents
Segment drop = segment current × segment loop resistance
Node voltage = parent voltage − segment drop
Segment loss = segment current² × segment loop resistance

The current sum follows conservation of charge at each branch. Drops accumulate from the source through the node’s ancestry; drops on unrelated branches are not subtracted from that node. These relationships follow series/parallel circuit principles and V = IR.

Two nodes in a chain

Use a hypothetical 12 V source. Node 1 has a 1 Ω loop segment from the source and a local 0.1 A load. Node 2 has a 1 Ω loop segment from node 1 and a local 0.2 A load.

Node Segment current Segment drop Node voltage
1 0.1 + 0.2 = 0.3 A 0.3 V 11.7 V
2 0.2 A 0.2 V 11.5 V

Conductor loss is 0.3² × 1 + 0.2² × 1 = 0.13 W. The source current is 0.3 A, not the sum of both segment currents, because the second load is already included upstream.

A zero or negative node voltage

The arithmetic can produce nonpositive node voltage if the stated constant current requires too much drop. That flags an unusable assumed operating point at that node. A negative value is not a prediction that a passive wire run creates a reverse-polarity supply. Even a positive voltage does not establish that a device will operate within its specified range.

Supported network and limits

The model assumes independent outgoing/return segment pairs represented by their loop resistances. It does not solve shared-return coupling, rings, multiple sources, regulators, voltage-dependent devices, or source droop. Obtain resistance at the relevant conductor temperature and include known connection resistance as appropriate to your segment definition.

Source voltage must be positive; segment resistance and local current can explicitly be zero. Up to 30 nodes are supported. Parent references, all required values, and row structure are validated. Calculations and status checks use unrounded values; table displays round to three decimals. For a single uniform run with one far-end load, use the simpler two-wire model.