DC converter load calculator

Calculate source-side current, input power, and loss from output voltage, current, and the efficiency you supply.

Your inputs

Use decimal values in the labeled units. Fractions, scientific notation, and missing values are not treated as valid numbers.

Nonnegative load current on the converter output side.
Explicit efficiency at this load; greater than 0 and no more than 100.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

Your results will appear here after calculation.

Steady DC conversion at the efficiency you provide for this operating point. Output current and voltage are on the load side. Do not add the same converter loss twice or assume efficiency applies at every load.

Translate an output load to the source side

A DC converter changes the relationship between load-side and source-side current. The output current cannot simply be entered as battery or source current when the voltages differ. Use output voltage and current together with the conversion efficiency at that operating point.

For source voltage Vs, output voltage Vo, output current Io, and efficiency η expressed as a fraction:

Output power Po = Vo × Io
Source power Ps = Po ÷ η
Source current Is = Ps ÷ Vs
Converter loss = Ps − Po

The efficiency input is a percentage, so the calculation divides it by 100 first. The relationships combine electrical power P = VI with the definition of efficiency as useful output power divided by input power. No efficiency is assumed from the converter’s type or brand.

Six watts at 80 percent efficiency

With a hypothetical 12 V output, 0.5 A output current, 80% efficiency, and 24 V source:

  • Delivered power is 12 × 0.5 = 6 W.
  • Source power is 6/0.8 = 7.5 W.
  • Source current is 7.5/24 = 0.3125 A, displayed as 0.313 A.
  • Converter loss is 7.5 − 6 = 1.5 W.

At 100% efficiency, the same output requires 6 W and 0.25 A from the source, with zero conversion loss. That is an ideal boundary case, not an assertion that real hardware is lossless.

Use efficiency for the actual operating point

Efficiency may vary with load, input voltage, temperature, and device behavior. This tool uses the value you enter without independently modeling those changes. A zero output current produces zero under the proportional model; it does not estimate a converter’s no-load or quiescent consumption.

The source and output voltages must be positive, output current nonnegative, and efficiency greater than zero and no more than 100%. Decimal values are required. Exact arithmetic precedes three-decimal display rounding, and displayed current is not reused to calculate loss.

When adding the result to a source-side load budget, include the converter input once; do not also add the same downstream load or conversion loss a second time. For an enclosure, only loss released inside belongs in the cabinet heat calculation, not all power delivered to external equipment. Startup, current limits, voltage ranges, protection, and product selection remain separate checks.