Count heat released inside the cabinet
Power delivered through an enclosure to an external lock is not automatically heat inside that enclosure. The relevant load is the actual loss released by internal equipment, including a converter’s inefficiency. This tool separates direct internal losses from conversion losses to avoid treating all supply output as cabinet heat.
Enter measured or otherwise supported internal dissipation per unit for the direct-loss list. For converters physically inside the cabinet, enter delivered output power and efficiency at that operating point. Do not list the same converter loss in both lists.
Direct internal heat = Σ(quantity × internal watts per unit)
Converter heat = Σ[quantity × output power × (1/η − 1)]
Total heat rate = direct heat + converter heat
η is efficiency as a fraction. The converter term comes from input minus output power, using electrical power and energy conservation. The tool also reports energy released in one hour: 1 W sustained for one hour = 3.6 kJ.
A small cabinet loss budget
Suppose two hypothetical internal devices each dissipate 1 W, and one internal converter delivers 6 W externally at 80% efficiency.
The converter takes 6/0.8 = 7.5 W and loses 1.5 W. Total internal heat is 2 × 1 + 1.5 = 3.5 W. In one hour that rate releases 3.5 × 3600/1000 = 12.6 kJ.
Adding the 6 W delivered to the external load would overstate cabinet heat for this defined boundary. If that load were actually inside the cabinet and released its power as heat there, its supported internal dissipation would belong in the direct list instead.
Compare heat rates in watts and BTU per hour
The same internal loss can be expressed in watts or BTU_IT/h, meaning International Table British thermal units per hour. Both describe a rate of heat release. A BTU by itself is an amount of energy; BTU/h is a rate, just as watts are joules per second. Neither unit supplies the enclosure’s temperature rise.
NIST SP 811, footnote 9 defines 1 BTU_IT = 1,055.05585262 J exactly. Therefore, BTU_IT/h = watts × 3,600 / 1,055.05585262. The multiplier is approximately 3.412142, but the calculation uses the exact energy conversion before display rounding. The thermochemical BTU is a different unit; check which convention a product document uses before comparing figures.
The hypothetical 3.5 W budget above is 11.942 BTU_IT/h at three-decimal rounding. If sustained for one hour, it releases 12.600 kJ, or approximately 11.942 BTU_IT of energy. Changing the displayed unit does not add a cooling allowance or make the external 6 W load part of this cabinet’s heat budget. Retain the original watts and operating condition when transferring this loss figure into a separate thermal model.
Heat rate does not determine temperature rise alone
The same watts can produce different internal temperatures depending on enclosure size, material, ambient temperature, solar exposure, ventilation, mounting, and heat paths. This calculator does not model those factors or select fans, vents, cooling equipment, or an enclosure rating.
Use efficiency for the stated load; no-load consumption is not inferred. Entering zero output with 100% efficiency explicitly contributes zero under this model. It does not claim a real converter consumes nothing at standby.
Each list supports up to 30 rows, whole-number quantities from 1 to 1,000, and nonnegative power. Efficiency must be greater than 0 and at most 100%. Use decimal values; results retain exact arithmetic before three-decimal display rounding. The converter load calculator provides the related source-side current calculation.