Two-wire DC voltage drop calculator

Calculate two-wire DC voltage drop, a theoretical one-way length limit, or compare supplied conductor candidates against an explicit minimum load voltage.

Your inputs

Voltage at the source terminals under the stated load.
Stated constant current in both paths. Zero is allowed in voltage-drop mode; length and comparison modes require a positive current.
Source to load only. The calculation includes an equal return length; do not double your input.
Use the actual conductor’s DC resistance at the relevant temperature. This must not be a loop-resistance value.

Two equal conductors, one load at the far end. No wire-gauge or material defaults are assumed.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

See the calculated loop resistance, voltage drop, and load-end voltage.

A constant-current, resistive DC model, not a wire-size or compatibility approval. Source regulation, connections, temperature changes, and actual device behavior require separate checks.

Define one outgoing and return run

Calculate resistive voltage drop for a DC circuit with one load at the far end of two equal conductors. Enter the source voltage, a stated load current, the one-way cable length, and DC resistance per unit length of one conductor at the relevant temperature.

The calculator includes the equal return path. Do not double the entered length, and do not enter a resistance figure that already includes both conductors.

Choose the resistance basis

Use a verified resistance value appropriate to the actual conductor material, cross section, construction, and temperature. Supported units are ohms per 1,000 ft and ohms per km. Length can be entered in feet or meters independently of the resistance unit; the calculator converts the length first.

No AWG table, copper default, ambient temperature, or allowable percentage drop is assumed. A wire’s DC resistance is not its ampacity. A positive calculated terminal voltage does not establish that a device can operate at that voltage.

Loop resistance and drop

For one-way length L, single-conductor resistance per unit length r, load current I, and source voltage Vₛ, use matching length units:

Loop resistance R = 2Lr
Voltage drop ΔV = IR
Calculated load-end voltage = Vₛ − ΔV
Drop percentage = 100 × ΔV ÷ Vₛ
Calculated wire loss = I²R

The current is treated as constant through the full outgoing and return paths. Actual electronic loads can change current with voltage, stop operating, or cycle. Source resistance, regulation, connections, switches, and fuses add effects not included in this wire-only model.

Read zero and negative results

If the calculated drop equals the source voltage, the model leaves zero volts for the load. If drop exceeds the source voltage, the negative arithmetic value signals that the assumed current is inconsistent with a usable operating point. It does not predict an actual reverse-polarity supply. Revisit the current, resistance, and circuit model rather than using that result as a device voltage prediction.

The status uses unrounded values. For example, a tiny positive voltage can display as 0.000 V while its exact value remains positive. Check the exact result as well as the three-decimal display.

Find the maximum one-way length for a stated minimum voltage

Choose maximum one-way length when you already know the minimum voltage required at the load terminals for the actual device and operating state. The tool rearranges the same equal-conductor relationship; it does not choose a universal percentage drop or a wire size.

Maximum one-way length = (source voltage − stated minimum load voltage) ÷ (2 × current × single-conductor resistance per unit length)

The current must be positive in this mode. With zero current, wire drop is zero at every length in this ideal model, so there is no finite voltage-drop length limit to calculate. The stated minimum must be positive and cannot exceed the source voltage. If the two voltages are equal, the available wire-drop budget is zero and the calculated maximum length is zero.

For hypothetical 24 V at the source, 20 V required at the load, 1 A, and 10 Ω/1,000 ft per conductor, the available drop is 24 − 20 = 4 V. Single-conductor resistance is 0.01 Ω/ft, so the length is 4 ÷ (2 × 1 × 0.01) = 200 ft, exactly 60.96 m. At 199 ft the model leaves 20.02 V; at 200 ft it leaves 20 V; at 201 ft it leaves 19.98 V. These are arithmetic examples, not conductor or device specifications.

The unrounded length is the mathematical boundary for these exact inputs. A three-decimal rounded length can round upward; it is not an allowable cut length. If the same example uses 3 Ω/1,000 ft and a 22 V minimum, the exact boundary is 1,000/3 ft, displayed as 333.333 ft. Keep the exact value and actual measurement uncertainty with the record. Source variation, connection resistance, temperature, inrush, and device behavior can consume voltage margin and are outside this calculation.

If a finished-cable resistance value is unavailable, the wire resistance calculator provides a separate uniform-material estimate from applicable resistivity and conductive area. Prefer data for the actual cable construction when available. Use a branch network when different segments carry different downstream currents.

Compare cables against the same voltage requirement

An access-control wire-size question has a useful first comparison: how much voltage would each candidate leave at the load under the same stated current, length, source voltage, and resistance conditions? Candidate comparison applies the two-wire relationship separately to each supplied single-conductor resistance. A label such as an AWG size identifies a candidate; it does not supply its resistance or establish its ampacity.

Record the actual cable product and resistance source for every row. All resistance values need a common temperature and condition basis. OpenStax’s resistance discussion explains why resistance depends on material, dimensions, and temperature. Comparing one cable’s cool-condition resistance with another’s hot-condition value can confuse a condition difference with a cable difference. The separate wire resistance calculator can apply a supplied linear temperature relationship when that approximation and its parameters apply; no temperature correction occurs inside this comparison.

For a hypothetical 24 V source, 20 V minimum, 1 A, and 100 ft one-way, these invented resistance values give:

Candidate Single-conductor resistance (Ω/1,000 ft) Loop resistance (Ω) Load-end voltage (V) Margin above 20 V (V) Theoretical maximum one-way length (ft)
A 10 2 22 +2 200
B 20 4 20 0 100
C 25 5 19 −1 80

Each margin is load-end voltage − stated minimum. For A, 24 − 2 × 100 × 0.01 × 1 = 22 V, so its margin is 22 − 20 = +2 V. B is exactly at the supplied minimum and has no modeled voltage margin. C falls below it. Lower resistance reduces drop and wire loss at this fixed current, and increases the theoretical length boundary; none of these outcomes selects a wire or proves the device starts successfully.

Statuses use the unrounded margin. A resistance of 20.000000000001 Ω/1,000 ft in this example leaves 19.9999999999998 V: the display reads 20.000 V, but the status correctly remains below the minimum. Equality is a mathematical boundary, not an added tolerance. Retain the exact margin, source conditions, and actual device voltage requirement when reviewing a candidate. Heating, protection, connection loss, and installation requirements remain separate checks.

Check forward voltage-drop examples

All resistance values below are hypothetical arithmetic examples, not wire data or recommendations.

Feet and ohms per 1,000 ft

Use 24 V, 1 A, 100 ft one-way, and 10 Ω/1,000 ft per conductor:

R = 2 × (100 ÷ 1000) × 10 = 2 Ω.

Drop is 1 × 2 = 2 V; load-end voltage is 24 − 2 = 22 V; percentage drop is 100 × 2/24 = 8⅓%; wire loss is 1² × 2 = 2 W.

Displays are 2.000 Ω, 2.000 V drop, 22.000 V load-end, 8.333%, and 2.000 W loss. A one-way input of 30.48 m with the same Ω/1,000 ft resistance gives the same result because 1 ft is exactly 0.3048 m.

Meters and ohms per km

Use 100 m one-way and 10 Ω/km with the same 24 V and 1 A. The calculation is 2 × (100 ÷ 1000) × 10 = 2 Ω, so the outputs match the first example. The resistance values have different physical meanings; their numbers happen to give equal loop resistance for these two different lengths.

Current and feasibility

For a 2 Ω loop at 2 V, a stated 1 A produces a 2 V drop and zero calculated load-end voltage. At 1 V, the same assumption produces −1 V. Both cases need a different operating-current assumption or circuit model; neither demonstrates successful device operation.

Input and application limits

Source voltage and per-conductor resistance must be positive. In voltage-drop mode, current and one-way length may be zero, but must be entered explicitly. Maximum-length and candidate-comparison modes require positive current and an explicit positive minimum voltage no greater than the source. Comparison also requires the common resistance conditions and a source/product record for each of 1–20 uniquely labeled candidates. Numeric inputs are decimal numbers, up to 64 characters and 12 decimal places. Results use exact rational unit conversion and arithmetic, followed by three-decimal half-up display rounding. Nonterminating exact values remain fractions.

Use this model for a stated steady DC load at the end of a uniform, equal two-conductor run. Unequal conductors, shared returns, distributed loads, branches, AC impedance, transient inrush, and changing temperatures need more detailed models. The tool does not check conductor heating, ampacity, protection, manufacturer voltage limits, or installation compliance.

If you need a current total first, use the DC load budget calculator. Do not put a whole installation’s current through one cable unless that cable actually carries it.

FAQs

Why is there a factor of two?

The current travels to the load and back. The tool assumes the two conductors have equal length and resistance per unit length, so the total wire resistance is twice one conductor’s resistance.

Can I enter the measured loop resistance directly?

This form expects resistance per unit length of a single conductor. Entering a complete loop measurement as if it were a per-conductor value would produce the wrong result. Use a suitable direct-resistance calculation for that different input.

Sources

OpenStax, University Physics Volume 2, §9.4, Ohm’s law explains V = IR and its applicability to ohmic materials. §10.2, Resistors in series and parallel explains series resistance and wire IR drops. §9.5 supports resistive power loss. These support the model, not wire material data. Exact foot and meter relationships are documented in References.