Wire Resistance Calculator

Calculate uniform-conductor or equal two-wire loop resistance from length, conductive area, supplied resistivity, and optional linear temperature adjustment.

Your inputs

Use decimal values in the labeled units. Fractions, scientific notation, and missing values are not treated as valid numbers.

Nonnegative decimal; do not double the length for loop mode.
Positive actual conducting area, excluding insulation and voids. No automatic AWG conversion.
Positive decimal. Multiply Ω·m by 1,000,000 to use this unit. Record the source and reference temperature.
Nonnegative decimal referenced to the same temperature as resistivity, within its stated range.
Signed decimal difference, not absolute temperature.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

Your results will appear here after calculation.

Uniform conductor and user-supplied resistivity at a known reference temperature. A loop uses two equal conductors of the entered one-way length. Optional linear adjustment requires a valid coefficient and temperature range. No terminals, splices, ampacity, AC effects, or installation approval.

Estimate resistance before calculating voltage drop

A door-access cable run can lose voltage in both its outgoing and return conductors. This tool estimates the conductor contribution when you know its conductive area and material resistivity. If the cable manufacturer already supplies DC resistance for the actual construction and temperature, use that data directly in the two-wire voltage drop calculator.

This is a uniform-conductor model. It does not choose a wire size, determine ampacity, or establish whether an electric lock will operate. An AWG label alone is not an input to this calculation; the actual conducting area and applicable resistivity are required.

Length, cross-sectional area, and resistivity

OpenStax, University Physics Volume 2, §9.3 gives the uniform-conductor relationship:

Single-conductor resistance R = ρ × L ÷ A

Here L is the length of one conductor in meters, A is its conductive cross-sectional area in mm², and ρ is resistivity in Ω·mm²/m at a specified reference temperature. Longer conductors have more resistance; a larger conducting area gives less resistance for the same material and length.

The area excludes insulation, jacket, and spaces between strands. It is not the area calculated from the outside diameter of an insulated cable. A stranded or plated cable may require construction-specific data rather than an ideal bulk-material estimate.

If your source gives resistivity in Ω·m, multiply its numerical value by 1,000,000 for the Ω·mm²/m field. For example, 0.00000002 Ω·m = 0.02 Ω·mm²/m. This conversion is a demonstration, not an assigned material property. Scientific notation is not accepted in the fields; use ordinary decimals.

Single conductor or equal outgoing-and-return pair

Select single conductor for one piece of wire. Select two equal conductors only when the outgoing and return conductors have the same length, area, resistivity, and temperature. Enter the one-way length once; the tool adds the two equal resistances.

Unequal conductors must be calculated separately and added. The selected path result excludes terminal, splice, contact, source, and device resistance. Keep the single-conductor and loop record with the result so the return is not counted twice later.

Feet convert to meters using the exact relationship 1 ft = 0.3048 m, documented in the unit references. Selecting a different length unit reinterprets the typed number; it does not convert it automatically.

Optional linear temperature adjustment

OpenStax §9.3 also describes the approximate resistance relationship:

R(T) = R(reference) × [1 + α × (T − T(reference))]

Enter a nonnegative resistance temperature coefficient per °C, referenced to the same temperature as the resistivity. Enter a signed Celsius temperature difference: cooling is negative. Use this only within the range where your source supports a linear approximation. A positive computed factor is necessary but does not prove the source remains valid over that range.

This model does not separately expand the length and cross-section. It uses the stated resistance coefficient directly; do not substitute a linear thermal expansion coefficient. Choose reference-temperature mode when no valid resistance coefficient is available. Inactive temperature fields do not affect that mode.

Check a hypothetical 100-foot route

Assume one-way length 100 ft, conductive area 1 mm², reference resistivity 0.02 Ω·mm²/m, resistance coefficient 0.004 per °C, and a 25°C increase. These are arithmetic examples, not cable specifications.

Step Independent calculation Result
One conductor length 100 × 0.3048 30.48 m
Reference resistance 0.02 × 30.48 ÷ 1 0.6096 Ω
Temperature factor 1 + 0.004 × 25 1.1
One conductor at stated temperature 0.6096 × 1.1 0.67056 Ω
Equal two-conductor loop 2 × 0.67056 1.34112 Ω
One conductor per 1,000 ft 0.02 × 304.8 × 1.1 ÷ 1 6.7056 Ω/1,000 ft

The main loop display rounds to 1.341 Ω. The unrounded value remains available; a displayed 0.000 is not proof of exactly zero resistance. Entering 30.48 m gives the same physical result. With zero length, path resistance is exactly zero while the per-length material result remains nonzero.

For DC voltage drop, use the single-conductor per-1,000-ft value and one-way length. For a DC branch network, use the complete loop resistance for each segment. Retain the source, reference temperature, coefficient, path definition, and full precision with the record. Real cable limits, device voltage requirements, and connection losses still need separate verification.