DC timeline charge calculator

Calculate amp-hours, watt-hours, and average current across a nonoverlapping timeline of stated DC load phases.

Your inputs

Use decimal values in the labeled units. Fractions, scientific notation, and missing values are not treated as valid numbers.

One duration (hours), total current (A), voltage (V) per line. Up to 30 nonoverlapping phases. Enter zero explicitly for an off phase. All values are nonnegative; total duration must be positive.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

Your results will appear here after calculation.

Nonoverlapping chronological phases at the same defined electrical boundary. Each row is a whole-system current and voltage for that phase. Combine simultaneous devices first; do not count overlapping hours twice. No battery runtime guarantee is implied.

Add time phases without counting the same hours twice

A system’s current can change over a shift or operating cycle. This tool divides the timeline into nonoverlapping phases and accumulates charge and energy. Each row describes the whole-system current and voltage at the same electrical boundary during that phase.

If several devices run at once, first combine their currents for that interval with the DC load budget. Do not enter each device’s overlapping hours as separate chronological phases here; doing so would make the total timeline duration incorrect.

Total hours T = Σti
Charge Q = Σ(Ii × ti), in Ah
Energy E = Σ(Vi × Ii × ti), in Wh
Average current = Q ÷ T

These relationships follow the definition of electric current as charge per time and power as VI. Ah and Wh measure different quantities. Phases with different voltages can have the same charge but different energy.

A twelve-hour hypothetical timeline

For 10 hours at 0.1 A and 12 V, followed by 2 hours at 0.5 A and 12 V:

Quantity Independent calculation Result
Duration 10 + 2 12 h
Charge 0.1 × 10 + 0.5 × 2 2 Ah
Energy 12 × 0.1 × 10 + 12 × 0.5 × 2 24 Wh
Average current 2 ÷ 12 0.167 A displayed

An explicit off phase with zero current adds time without adding charge. Omitting that phase changes the average, even though charge may remain the same. A zero-duration row contributes nothing, but the combined timeline must have positive duration.

Keep all phases on the same side of conversion

Battery-side current and a downstream converter’s output current are not interchangeable. Convert operating points to the same boundary with the DC converter tool before building the timeline. Include standby, losses, and simultaneous loads only when they are represented in your stated currents.

The result is an accounting total for the entered timeline, not usable battery capacity or guaranteed runtime. Temperature, discharge rate, cutoff voltage, aging, and actual load changes require separate data. For a single constant-current baseline, use the ideal battery calculator.

Up to 30 phases are supported. Duration uses decimal hours, not clock notation; current and voltage are in A and V. All values must be nonnegative and present. Results use unrounded sums with three-decimal half-up display rounding.