Plan two equal bends for a parallel shift
An access-control pathway may need to shift toward a box or clear an obstruction while continuing in the same direction. A two-bend offset makes that shift with equal, opposite bends in one plane. This calculator estimates mark spacing and shrink allowance using the five angle rows in the Klein Tools Conduit Bender Guide, pages 6–8.
Use it with that guide’s reference-end and arrow-mark procedure when the guide applies to your bender and conduit. The result is a marking estimate. The calculator does not determine whether a particular bender can make the offset, whether the marks leave enough working space, or whether the completed pathway meets installation requirements.
Keep offset height and distance to the obstacle separate
Offset is the perpendicular shift between the parallel portions of the run. It is not the diagonal length between bends. Include any necessary clearance in the offset you establish from the actual installation; the tool adds no clearance automatically.
Distance to obstacle is measured from one reference end as shown on page 6 of the guide. Page 7 places the first mark at that distance plus shrink. The second mark is closer to the same reference end, separated from the first by the calculated spacing. Both output coordinates use that one end; the distance between marks is not itself a second coordinate.
Spacing = offset × guide multiplier
Shrink allowance = offset × guide shrink factor
First mark = distance to obstacle + shrink allowance
Second mark = first mark − spacing
A second mark below zero would fall beyond the reference end. The calculator rejects that layout rather than reporting an impossible negative mark. A mark at zero is arithmetically valid, but the physical bender still needs its required engagement and working room.
Why these factors differ from exact trigonometry
The guide gives practical table factors for 10°, 22.5°, 30°, 45°, and 60° bends. For example, its 45° spacing multiplier is 1.4 and shrink factor is 3/8 per unit offset. Those are the values used here. They are not replaced with a zero-radius triangle’s 1/sin(45°) and tan(22.5°).
For the shrink rows, the printed fractions 1/16, 3/16, 1/4, 3/8, and 1/2 are used exactly in arithmetic. The guide also prints rounded decimals for the first two fractions; 1/16 is 0.0625, not exactly 0.063. This preserves the stated fractional basis without suggesting the bending estimate itself is exact.
At a fixed angle, doubling the offset doubles both spacing and shrink allowance. Changing the distance to the obstacle moves both marks equally without changing their separation. Changing angle uses a different guide row; it does not interpolate an unlisted bend angle.
Follow the guide’s six-inch example
For a 6 in offset, 20 in distance to the obstacle, and two 45° bends, pages 6–7 give:
| Quantity | Calculation | Result |
|---|---|---|
| Distance between marks | 6 × 1.4 | 8.4 in |
| Shrink allowance | 6 × 3/8 | 2.25 in |
| First mark from reference end | 20 + 2.25 | 22.25 in |
| Second mark from reference end | 22.25 − 8.4 | 13.85 in |
The same physical inputs are 152.4 mm and 508 mm. They produce 213.36 mm spacing, 57.15 mm shrink, and marks at 565.15 mm and 351.79 mm. Inch and millimeter outputs use the exact conversion 1 in = 25.4 mm; the guide’s practical approximation remains in both units.
Lengths display to three decimals. That display precision is not a bending tolerance or permission to trim to the displayed value. Keep the original measurements and guide with the record.
Check the completed pathway separately
The cited guide discusses correct bender size, arrow alignment, keeping bends in one plane, and springback. Use the applicable manufacturer instructions for those physical operations. This tool does not add a universal take-up, bend radius, springback correction, conduit diameter, or code limit.
After establishing the actual route, the pathway occupancy calculator can account for circular cross-sectional areas. The cable-run input guide explains the separate current-path and resistance information needed for voltage-drop calculations. Mark spacing does not determine electrical cable length or permitted pathway fill.