Two explicitly defined supervision circuits
“EOL” and “DEOL” do not specify every manufacturer’s wiring or state thresholds. This tool calculates only the two resistor/contact arrangements written below. Match the actual controller documentation before using a resistance result to interpret an input.
The contact is normally closed in the modeled normal state. Wires and closed contacts have ideal zero resistance; an open contact has ideal infinite resistance. Resistor tolerances and cable resistance are omitted.
Single end-of-line topology
The EOL model has R1 in series with the alarm contact. With the contact closed, loop resistance is R1. Opening that contact breaks the circuit. A broken series wire also produces an open circuit, so these two physical conditions have the same ideal resistance in this topology.
Double end-of-line topology
The DEOL model has R1 in series with a parallel pair consisting of the alarm contact and R2. A closed ideal contact bypasses R2, giving R1. When the contact opens, the remaining path passes through both resistors, giving R1 + R2. A separate series tamper contact, if present, opens the whole loop.
These results follow series and parallel resistance relationships. They do not imply that a particular panel recognizes the resulting states.
Example state table
For hypothetical R1 = 1,000 Ω and R2 = 2,000 Ω:
| Physical model state | EOL | DEOL |
|---|---|---|
| Alarm contact closed | 1,000 Ω | 1,000 Ω |
| Alarm contact open | Open circuit | 3,000 Ω |
| Series wire broken or series tamper open | Open circuit | Open circuit |
| Ideal short directly across panel terminals | 0 Ω | 0 Ω |
The short-circuit row refers specifically to a short across the panel terminals. A short at some other point in the wiring can bypass a different combination of components and is not represented by that row.
Resistance and recognized state are separate
Real controllers use product-specific thresholds and wiring arrangements. The tool does not load those thresholds, determine resistor placement, or label an entered resistance as a valid controller state. Different contact types, alternate resistor arrangements, multiple contacts, and fault combinations need their actual circuit model.
R1 must be positive. R2 must also be positive in DEOL mode and is ignored in EOL mode. Inputs are decimal ohms; displayed finite values round to three decimals. Open circuit is reported as a state rather than a large invented numeric resistance. For voltage/current relationships at a defined operating point, use the DC Ohm’s law calculator.