Ideal capacitor hold calculator

Calculate ideal capacitance for a constant-current interval and an explicit allowed capacitor voltage drop.

Your inputs

Use decimal values in the labeled units. Fractions, scientific notation, and missing values are not treated as valid numbers.

Nonnegative load current.
Nonnegative interval.

Enter your values or load the labeled example.

Your result

Waiting for your inputs

Your results will appear here after calculation.

Ideal capacitor supplying a constant current directly; no converter, ESR, leakage, tolerance, minimum device voltage, or product hold-time guarantee. Allowed voltage drop must be positive.

Charge taken from a capacitor causes voltage drop

For a capacitor directly supplying a constant current, charge removal is proportional to time. This simple model can establish a theoretical hold-up baseline at a stated capacitor node. It is different from a battery amp-hour budget or a regulated constant-power load.

Charge and voltage

Removed charge = current × time
Ideal capacitance = current × time / allowed voltage drop

This follows Q = CV. For 0.1 A, 0.1 s, and 1 V allowed decrease, required ideal capacitance is 0.01 F = 10,000 µF. Zero current or zero duration yields zero in this ideal arithmetic; positive voltage drop is still required.

Exact decimal arithmetic precedes three-decimal display. Real hold-up depends on initial voltage, device undervoltage limits, capacitor tolerance, ESR, leakage, aging, temperature, inrush, and any converter’s efficiency/control. This tool does not select a capacitor voltage rating or guarantee a lock/controller’s hold time.